| Cell Power Co., Ltd. |
|
Item Number:
|
TU series |
|
Product Name:
|
TU series |
|
Description:
|
Advanced self-diagnostics with outstanding reliability, the TU series True On-Line UPS helps
users to deal with annoying power problems. Therefore, regions with poor main power quality will benefit and improve dramatically with this cost-efficient UPS. |
|
Features:
|
1.IGBT devices adopted ensure system performance.
2.20MHz SPWM design with double conversion technology.
3.Improved ventilation system to avoid any dust from accumulating.
4.PLL design, parallel operation with STS ensures highest degree of reliability.
5.Microprocessor controlled integrated LCD display with light touch operations.
6.Intelligent short circuit protection.
7.Complete noise and surge suppression.
8.Warning design with history recording of power status.
9.RS-232 communication interface. |
|
Specification:
|
Capacity P.F= 0.8
TU-8K TU-10K TU-12K TU-15K TU-20K TU-25K TU-30K TU-40K TU-50K
6.4KW 8KW 9.6KW 12KW 16KW 20KW 24KW 32KW 40KW
INPUT
Voltage 100/110/115/120/220/208/380/416/460 VAC ?20%
Frequency 50Hz ?5% or (60Hz ?5%)
Phase 1P2W+G or 3P3W + G or 3P4W+ G
BATTERY
DC Voltage Normal 192VDC (160-220VDC)
Type Sealed Lead Acid Maintenance Free
Autonomy 10 min (additional batteries can be placed for extended autonomy time)
Recharge 10hrs to 90% After fully discharged
OUTPUT
Voltage 100/110/115/120/220/208/380/416/460 VAC
Frequency 60Hz or 50Hz
Phase 1P2W + G
Voltage Stability ?1% for combined effects of load and input voltage variation
Frequency Stability ?0.5% (AC Fault mode)
Power Factor 0.8 ~ 1 LAGGING
Transient Response ?4% (0 ~ 20% Sudden Change in Load)
?2% (20 ~ 100% Sudden Change in Load)
Crest Factor 3:1
Wave form Factor <3% (Linear Load)
Overload Capacity 100% ~ 125% 10 min continuos power supply
125% ~ 150% 30 sec
Efficiency AC to AC >90%
Transfer Time
Blackout Zero
UPS <---> Bypass < 1m sec
End of Overload UPS automatic restart
Audible Noise (TU-8K TU-10K ) < 50db Others < 55db
LED Indicator
UPS indication & Flow Chart Normal Input (green) Normal Inverter (green) Load Overpass (orange)
UPS Failure (red) Low Battery (red) Overload (red)
LCD Indicator
Status & Meter CPU digital detect & diagnose-information: model, input/output voltage, frequency, output current, power events records and analysis
Alarm System
Battery Discharge 2 various notifications
1. Utility fail, a beep every 4 sec.
2. Battery power near empty, a beep every sec.
Short Circuit Protection
Stop Inverter Instant Output Instead Of Going to Bypass
Environment
Temperature 0°C - - 43°C, 10% - - 90% RH (NON-CONDENSING)
Dimensions(LxWxH)
UPS 750 x 380 x 1065 (TU-8K TU-10K TU-12K) 700 x 650 x 1540 (TU-15K TU-20K TU-25K) 650 x 800 x 1690 (TU-30K TU-40K TU-50K)
Battery Case 750 x 330 x 1065 (TU-8K TU-10K TU-12K) 700 x 400 x 1540 (TU-15K TU-20K TU-25K) 800 x 800 x 1694 (TU-30K TU-40K TU-50K) |
|
|
|
|
|
|
 |
Send Message (Your message will be sent directly) |
|
|
|
|
|
|