| AC Power Corp. |
|
Item Number:
|
AEU-11003 / AEU-11003L |
|
Product Name:
|
AEU-11003 / AEU-11003L |
|
Description:
|
1. Output isolation transformer equipped
2. United operation mode available for battery diagnosis and generator
3. IGBT based rectifier/inverter
4. Input power factor >0.99, input current distortion < 3%
5 Dual DSP control
6. Super wide input window (-45%~+15%)
7. Distributed parallel technology, extend to 4 units without MSS
8. D-class surge suppressor equipped
9. Intelligent battery management
10. Class A EMC standard acquired
|
|
Specification:
|
|
Model
|
|
Model
|
AEU-11003 / 11003L |
|
Capacity
|
2KVA |
|
Input
|
|
Mode
|
Single phase |
|
Nominal Voltage
|
220Vac |
| Voltage Range |
- 160~276V, operation under full load
- 120~160V operation under linearly decreased load
- 120V operation under half load
|
| Frequency Range |
45~55Hz |
| Harmonic current distortion |
<4% |
| Power Factor |
0.99 |
|
Output
|
|
Power factor
|
Standard 0.7 (can reach 0.8) |
| Voltage |
220Vac ¡Ó 1% |
| THD |
Linear load < 3%; non-linear load <5% |
| Frequency |
When the mains frequency is within 50Hz¡Ó10%, the output
phase differential is less than 3 degrees; when the mains exceeds
the limitation or the battery is under operation, the output frequency
is 50Hz¡Ó0.2% |
| Peak factor |
3:1 |
| By pass operation voltage |
120~253Vac |
| Overload capacity |
5 min at 105~125% load, 10 sec at 125~150% load, 200
mS at >150% load |
|
Battery
|
| Unit efficiency |
90% |
| Model |
VRLA battery (12V/7Ah) |
| Number of embedded batteries |
10 |
| Rating voltage |
120Vdc |
| Backup time (full load) |
>10 min |
| Charging time (standard) |
8hs |
| Charging current (long backup time) |
5A can be expanded to 9A by parallel connection |
|
System
|
|
Power switchover time
|
0 |
| Dynamic voltage regulation |
≦5% of rating voltage at 0~100% load or 100% ~0 load |
| Bearable maximum input voltage |
320Vac, 1 hour (static) |
| Interference standard |
IEC 10000-4-2.3.4.5.11 Level III |
| System MTBF |
200,000 hours |
| Display |
LED display |
| EMC/EMI standard |
EN50091-2 CLASS-B |
| Safety standard |
CCEE, EN60950 |
| Noise (1m) |
<45dB |
| Surge protection |
Meets with IV installation requirement in IEC60664-1
regulations |
| Redundancy technology |
Hot backup through serial connection (6k, 10k) |
| Size (WxHxD) mm |
210 x 400 x 500 |
| Weight (standard type/long backup
time type) kg |
45/21 |
|
1. Additional features and options available, please contact our sales representative.
2. One year warranty.
3. All specifications are subject to change without notice.
4.Catalogue Download
|
|
|
|
|
|
|
 |
Send Message (Your message will be sent directly) |
|
|
|
|
|
|