Description:
The HLD01 (DD862) single-phase meter is designed to meet the IEC60521-1988 and BS EN 60521 standards for both indoor and outdoor installations. The meter with mechanical construction complying BS5685 is also available. With accuracy of class 2, it measures active energy in single-phase two-wire or three-wire alternating current power grids. Connection is direct or by instrument transformers. The average service life (MTTF) is 10 years and the maximum overload capacity is 500%Ib. The meter is KEMA certified and the design can be tailored to different customer requirements.

Features:
1. Meter case
Two types of cases are available. One is the insulating case of protective-class II and the other is the weather-proof case complying to IEC60529 and IP54.

2. Terminal block
The terminal block is molded of Bakelite. The voltage test link can be located inside or outside of the meter case. The maximum diameter of the terminal hole is 8. 5mm.

3. Driving element
The driving element consists of a voltage element and a current element, both of which are fixed to the frame. The voltage element has a low load adjustment mechanism, and the current element has an inductive load adjustment mechanism.

4. Rotor
The rotor shaft is made of aluminum alloy with a small hole in the upper end for storing lubrication and for fitting a brass bearing. The worm is turned of brass, and is acid-cleaned or nickel-plated. The worm and shaft can be detached.

5. Braking element
The magnet is made of AlNiCo5 alloy and designed as U-shaped so that the effect of short-time over current upon the magnet is negligible. The full load error can be fine controlled by adjustment mechanism.

6. Frame
The frame is die-casted by high-quality Si-Al alloy of stable property to avoid distortion. The application of static spray-painting on the surface prevents the frame from oxidation.

7. Upper bearing
The pin is made of high-quality abrasion-proof stainless steel and is embedded
On the brass pin base.

8. Lower bearing
Both double jewel bearing and magnetic bearing are available.

9. Register
The HLD01 meter with direct-reading cyclometer type register is available.
The register is self-located and is mounted on the frame by one screw. Fixing with two screws is also available but needs to be manually adjusted. There are two types of gears available: Brass gears and self-lubricating plastic gears.

10. Technical data
1 1Meter type HLD01 (or DD862)
12 Applicable Standards IEC60521. IEC514
13 Accuracy Class 2(according to IEC60521)
14 Average service life (MTTF): 10 years
15 (6) Basic current(Maximum current)A
16 5(6) 3(6) 5(20) 5(40) 10(60) 15(60) 20(80)
17 Rating current of transformer in 5A direct connection
18 Reference voltage Un: 110 V. 120V. 220V. 230V. 240V
19 Reference frequency fn: 50 Hz. 60 Hz
20 Power losses in voltage circuit at Un 50 Hz: 1.2 W/6 VA60 Hz: 1.0 W/5 VA
21 Power losses incurrent circuit at 50Hz Un Ib < 0.6 VA
22 Non-running with no-load 0.8~1.1Un
23 Starting current 0.5%Ib
24 Mean temperature coefficient: From 0. 1Ib to Imax at unity PF From 0.2Ib to Imax at unity 0.5 lagging <0.08%/0C<0.12%/0C
25 Insulation level: Withstanding A. C. Voltage for 50 Hz, 1min Withstanding impulse voltage 1.2/50us >2 kV (when bakelite base>4kV)>6kV (when bakelite base>8kV)
26 Rated load speed at unity PF, Ib 13.2 r/min
27 Rated load torque at unity PF, Ib 450uNm
28 Weight of rotor 24 g
29 Weight of meter 1.5 ~1.6kg
30 Meter base: Steel, Aluminum alloy, Bakelite
31 Meter cover: ABS, Aluminum, Glass, Bakelite, transparent PC
32 Terminal cover: ABS, Bakelite, PC
33 Register: Cyclometer single, Unidirectional, Jumping, and Metal
34 Option Reverse running stopper, pulse-sampling device


Safety Approval:
KEMA,ISO9000 etc.
Other Description:

HS Code: 90283010
Trademark: Holley
Model: HLD01 (DD862)
Standard: IEC 60521
Productivity: 2000Pcs/Day

 
 
Send Message   (Your message will be sent directly) 
* Required information     
* Subject :
* Message :
Contact Information  
* Please enter check code:

I want to post this inquiry to AsianNet trade bulletin for more opportunities.
Register to become a member; list your company and products for free!

 
Sun Asia Enterprise Co.,Ltd     Wonpro Co., Ltd.      Cheng Tung Industrial Co., Ltd.
Home - Global Suppliers - Best Products - Trade InfoCenter
Copyright (c) 2008 AsianNet Inc. All Rights Reserved.